biorem-projman-ovationdcs
Date: 2026 03-March 10
Ovation Graphics and Points
Known graphics:
- 2000AB.diag
- 2002.diag
- 4001.diag
- PLG6000.diag
- PLG6001.diag
- PLG6002.diag
- PLG6003.diag
Points
All points at the Maxson plant have the IESS suffix ".UNIT0@NET0"
Shown below are the IDCS values, which are equivalent to the IESS values but without this suffix.
biorem-projman-drop200-database-point-analysis
Points found in 4001.diag
There is a warning that 62 unresolved points exists, including: AAH4100, AAH4100-A, AAH4100-B, ..., AAH4100-J, AIR4100-01, AIR4100-02, ..., AIR4100-66, YS4100-A, YS4100-C
Take a backup from Drop 200.
On DROP 200, in cmd, run
sqlplus / as sysdba
Points found in 2000ab.diag
| IDCS | Category | Label | Unit |
|---|---|---|---|
| B1_AIT_6015 | Gas Detection | METHANE LEVEL | % |
| B1_AIT_6020 | Gas Detection | H2S LEVEL | PPM |
| B1_PIR_5000 | Inlet Signal | INLET PRESSURE | IN WC |
| B1_FIR_5000 | Air Flow | RECIRC AIR FLOW | SCFM |
| PT01100 | Air Flow | RECIRC AIR FLOW TOTAL 1 | SCF |
| B1_ZIT_5700_1 | Valve | RECIRC VALVE POSITION | % |
| B1_FIR_3000 | Waste Gas | WASTE GAS INLET FLOW | SCFM |
| B1_PIR_3000 | Waste Gas | WASTE GAS INLET PRESS | IN WC |
| B1_TIR_5400 | Discharge | DISCH GAS TEMP | °F |
| PT01100 | Discharge | DISCH GAS PRESS | IN WC |
| B1_FIR_5400 | Discharge | DISCH GAS FLOW | SCFM |
| B1_SIT_5100 | Blower #1 | BLOWER 1 SPEED | RPM |
| B1_SIT_5200 | Blower #2 | BLOWER 2 SPEED | RPM |
| B1_SIT_5300 | Blower #3 | BLOWER 3 SPEED | RPM |
| CH01088 | System | HEARTBEAT | Status |
Look in the spreadsheet for this purpose for point tracking.
Ovation Control sheets
Known control sheets:
It is as if the control sheets are missing.
which control sheets are these BR_ points used in? For all the points used in the biorem graphics, like the points used in pages 4001.diag, 2000ab.diag, 2002.diag, PLG6000.diag, PLG6001.diag, PLG6002.diag, and PLG6003.diag - in which various control sheets are these points used? What is the architecture of the biorem system that unifies these points and control sheets? You mentioned XML - is there some unified strucure and grouping and ornagization? it feels like these things are just painted across various graphics and control sheeets without another layer of documentation. It feels like a terrible case of "the code is the documentation"