ZLC-91001 - BLOWER 1 DAMPER CLOSE STATUS
Used on graphic 6091
Control Sheet Drop1/51, Control Task 2, Sheet "7000"
Add alarm when this is true, indicating that the valve is in close status
Guidance: The Damper should not be closed while the blower is running.
Guidance: Open the damper or turn off the blower.
Find an example alarm and duplicate it.
LAL-91401B
NUTRIENT TANK LEVEL LOW
System ID 8000048D3H
Signal Diagram Drop 1, Task 2 (7000) OCP 9100 Datalink
C:\Ovation\CtrlBldr\on-line\UNIT0\012A.svg
// install Edge on Drop212 to enable viewing of SVG files.
This Alarm when is bad when true - good quality when false.
Viewing SVG files on Ovation is not going well
How convenient that both ZLC-91001 and LAL-9140B are both on Sheet 7000
Q: Are alarms separate named points or are they only related to control points?
Okay I altered ZLC-91001 to have
- Config
- Status checking type: No Status Checking -> Alarm on 0 to 1 Transition
Fedex Account for Maxson and Stiles
Add line to Ovation SVG files in C:\Ovation\CtrlBuilder\on-line\UNIT0*.svg, to show in viewer as SVG vector based image.
<?xml version="1.0" encoding="UTF-16" ?>
<svg
xmlns="http://www.w3.org/2000/svg" # ADD THIS LINE
cb-classname="ControlFunction"
...
```